Heat pump installations for plumbing
This advisory note identifies common plumbing non-compliances in heat pump hot water installations across NSW. It provides practical guidance to assist licensed plumbers and contractors in meeting installation requirements.
Notes | 1/2025 |
Date issued | February 2025 |
Last updated | 14 March 2025 |
For | Licensees / Contractors / the Plumbing Industry |
Issued by | Building Commission NSW Building Specialist Compliance Unit |
Scope | Applies to all of NSW |
Notes 1/2025 |
Date issued February 2025 |
Last updated 14 March 2025 |
For Licensees / Contractors / the Plumbing Industry |
Issued by Building Commission NSW Building Specialist Compliance Unit |
Scope Applies to all of NSW |
Purpose
The purpose of this advisory note is to inform the plumbing industry of some common non-compliances found when Building Commission NSW inspectors conduct inspections of Heat Pump Hot Water installations.
Issue
Heat pump hot water installation
Reference
AS/NZS 3500.4:2021 - Plumbing and drainage, Part 4: Heated water services
Details of non-compliance 1
The termination of the temperature pressure relief drain
The TPR valve pipework terminated not as required in AS/NZS 3500.4:2021 – Clause 5.11.3. In some cases, the location of the discharge point could potentially scold the user, in others, the installation was detrimental to the system itself and the immediate surrounding building elements, adding possible financial burden to the property owner for repairs or replacement.
How to comply
Refers to AS/NZS 3500.4:2021 - Clause 5.11.3 Installation
Drain lines from temperature/pressure-relief valves, expansion control valves and tundishes shall be installed as follows:
- There shall be no tap, valve or other restrictions in any line.
- Each line shall fall continuously from the valve to the point of discharge.
- Drain lines from expansion control or temperature/pressure-relief valves shall not discharge into a safe tray.
- The point of discharge from each drain line shall be located so that the release of steam or hot water does not cause a nuisance, is readily discernible and incurs no risk of damage to the building or injury to persons.
- Where a drain line terminates outside a building, the end of the line shall be:
- not lower than 75 mm or higher than 300 mm above an overflow relief gully or disconnector gully;
- not lower than 75 mm or higher than 300 mm above a gravel pit not less than 100 mm in diameter;
- over a tundish in accordance with Item (h) below; or
not lower than 200 mm or higher than 300 mm above an unpaved surface.
Note: Where discharges from valves may adversely affect slabs and footings of buildings, the drain lines should discharge away from the building. Further guidance is provided in the National Construction Code (NCC).
- Where the drain line from the expansion control valve on a heat exchange water heater is directed into the water storage container, there shall be a minimum air gap of 20 mm, except where the valve and associated drain lines are supplied as an integral part of the water heater.
- Where a water heater is externally located, the drain line from the relief valve shall be terminated so as to discharge water away from the operator during operation of the valve.
- Where discharging over a tundish or gully, drain lines shall have an air gap of a size at least twice the diameter of the drain line.
- Where installed, plastics drain lines shall be:
- continuously supported;
- fixed and secured in accordance with Clause 4.5 - Support and fixing above ground;
- protected from UV if exposed to direct sunlight; and
installed with a suitable allowance for thermal movement.
Note 1: Typical installations of drain lines are illustrated in Figures 5.11.3(A) and 5.11.3(B).
Note 2: Ponding should be avoided.
Note 3: As the function of the temperature/pressure-relief valve on the water heater is to discharge high temperature water under certain conditions, the pipework downstream of the relief valve should be capable of carrying water exceeding 93 °C. Failure to observe this precaution may result in damage to pipework and property.
Details of non-compliance 2
The Heat Pump Hot Water system was not protected with a pressure limiting device.
Installations did not have pressure limiting valves (PLV) fitted. AS/NZS 3500.4:2021 - Clause 5.9.2 requires the installers to test inlet pressure and ensure a PLV is installed when required. When the inlet pressure requires a PLV however one is not installed, excess pressure may cause the TPR valve to fail and/or the tank itself to leak, this may be detrimental to the system itself and the immediate surrounding building elements also resulting in possible financial burden to the property owner for repairs or replacement.
How to comply
Refers to AS/NZS 3500.4:2021 - Clause 5.9.2 Required set pressure of valves (for unvented water heaters)
The required set pressure of expansion control valves, expansion vessels and inlet-pressure-control valves shall be determined from the set pressure of the temperature and pressure-relief valve supplied with the water heater with reference to Table 5.9.1(B).
Table 5.9.1 (B) - Set pressures for valves
Temperature/pressure-relief valve or pressure-relief valve setting | Without expansion control valve | With expansion control valve | Inlet pressure control valve type required | |||
---|---|---|---|---|---|---|
Maximum mains pressure | Inlet valve maximum setting | Exp. Control valve setting | Maximum mains pressure | Inlet valve maximum setting | ||
kPa | kPa | kPa | kPa | kPa | kPa | |
Open vent | N/A | 35 | N/A | N/A | N/A | Pressure reducing |
56 | N/A | 45 | 46 | N/A | 35 | Pressure reducing |
74 | N/A | 65 | 65 | N/A | 55 | Pressure reducing |
Open vent | N/A | 76 | N/A | N/A | N/A | Pressure reducing |
80 | N/A | 65 | 65 | N/A | 50 | Pressure reducing |
85 | N/A | 70 | 70 | N/A | 55 | Pressure reducing |
100 | N/A | 85 | 85 | N/A | 70 | Pressure reducing |
115 | N/A | 100 | 100 | N/A | 85 | Pressure reducing |
120 | N/A | 110 | 110 | N/A | 100 | Pressure reducing |
130 | N/A | 115 | 115 | N/A | 100 | Pressure reducing |
150 | N/A | 130 | 130 | N/A | 115 | Pressure reducing |
180 | N/A | 160 | 160 | N/A | 140 | Pressure reducing |
215 | N/A | 195 | 195 | N/A | 175 | Pressure reducing |
500 | 400 | 350 | 400 | 350 | 300 | Pressure reducing |
700 | 550 | 450 | 550 | 450 | 350 | Pressure reducing |
850 | 680 | 500 | 700 | 550 | 450 | Pressure reducing |
1000 | 800 | 600 | 850 | 680 | 500 | Pressure reducing |
1200 | 960 | 600 | 1000 | 800 | 600 | Pressure reducing |
1400 | 1120 | 600 | 1200 | 960 | 600 | Pressure reducing |
N/A | N/A | N/A | 1400 | 1100 | 600 | Pressure reducing |
Note: Where the maximum mains pressure is likely to be exceeded, inlet pressure-control valve shall be used.
Details of non-compliance 3
The hot, cold and TPR pipework was not insulated as required.
Installations had incorrectly fitted or no insulation installed. AS/NZS 3500.4:2021 - Clause 8.2.1 requires the pipework to be thermally insulated to help ensure the installed Hot Water Unit works as efficiently as possible.
How to comply
Refers to AS/NZS 3500.4:2021 - Clause 8.2.1 Piping associated with storage water heaters.
Piping shall be thermally insulated to achieve a minimum R-value as given in Table 8.2.1 for the climate regions identified in Appendix K for Australia and Appendix L for New Zealand, as follows:
- The inlet and outlet pipes, including valves, for a storage water heater, for at least the first 500 mm or, where an external heat trap is fitted, to a point 150 mm down the heat trap vertical leg closest to the water heater.
- All relief valves fitted directly to a storage water heater.
- The primary flow and return pipes, including valves, between an auxiliary heater and a storage water heater.
- All vent pipes to 300 mm above the maximum operating water level of the heated water system.
- On multiple installations, the whole heated water manifold, including valves, to a point at least 500 mm past the heated water outlet branch from the last water heater.
- On a solar water heater installation, the pipework between a solar pre-heater and an in-line supplementary water heater. The insulation installed in accordance with the above shall be installed so as not to impede the operation of the valves.
Note 1: Care should be taken to ensure the continuity of insulation at wall and roof penetrations. Insulation should be carried through roof penetrations into the ceiling area.
Note 2: In New Zealand, refer to NZBC Acceptable Solution H1/AS1 and NZS 4305.
Note 3: All exposed heated and cold-water piping to and from externally mounted water heaters in frost-prone areas may require additional insulation to prevent freezing.
Details of non-compliance 4
The hot water tank was installed not on a level, stable base as required.
Several instances were identified where the hot water tank was installed directly onto the dirt or not adequately supported. There were also instances where it had been installed leaning either sideways or forward off the wall due to the base and therefore the tank not being installed level.
How to comply
Refers to AS/NZS 3500.4:2021 - Clause 5.5.3 Support of water heaters or water storage tanks installed other than in a roof space or above a roof
Storage water heaters and cold-water storage tanks installed other than in a roof space or above a roof shall be floor-mounted or supported as follows:
- By brackets or hangers, designed to withstand the applied load.
- On a level, stable and impervious base designed and located to avoid ponding and made of:
- bonded brick or concrete cast in situ, having a thickness of not less than 75 mm; or
- pre-cast concrete having a thickness of not less than 50 mm.
- On a platform of timber, or other suitable and not less durable material.
Where such a platform is located at or near ground level, it shall be supported so that a clearance of not less than 100 mm is maintained from the surrounding ground.
Note: A typical platform construction is shown in Figure 5.5.3.
- In a recess in a wall structure able to withstand the applied load.
Important information for hot water systems installers in NSW
Below is key information for installers of hot water units, including heat pump types identified during Building Commission NSW heat pump inspections.
When installing hot water systems in NSW ensure you are referencing the current Australian Standards - AS/NZS 3500.1 and AS/NZS 3500.4 and the current Plumbing Code of Australia.
Where the hot water tank is to be installed internally whether concealed or not, refer to:
- AS/NZS 3500.4:2021 - 5.4.1 - Concealed water storage tanks
- AS/NZS 3500.4 2021 - 5.4.2 - Unconcealed water storage tanks
When installing two or more hot water tanks as a bank of storage heaters, refer to:
- AS/NZS 3500.4: 2021 - 5.10 - Multiple installations of pressure-type storage water heaters
Contact Building Specialist Compliance Unit (BSCU)
This advisory note has been approved for issue by the BSCU Technical Review Committee. Information contained within this document is current as of February 2025 and refers to codes and standards current at the time of writing.
Building Commission NSW disclaims any liability (including for negligence) to any person in respect of anything done, or not done, by that person in whole or partial reliance on any of the information in this advisory note.
More advisory notes on plumbing
- Floor waste and fixture requirements
- Drains in other than stable ground
- Use of flexible joints in drains
- General accessibility requirements
- Cross connection and backflow control
- Installing automatic air elimination valves
- Junctions at grade
- Tundish installation
- Automatic fire sprinkler system, design and installation - Domestic water supply
- Protection of fixtures where overflow relief gully height requirements cannot be met
- Code compliant and performance solution guideline
- Inspection openings
- Final audit inspection
- Installation requirements of Air Admittance Valves
- Point of connection explanatory notes
- Soffit requirements when connecting to a Sydney Water sewer main
- Installation requirements of temperature control devices